Sign In
2022 2nd Alert Hipo#23 Excavation of hard soil near by the HV cable, accidently hit on the live cable and got damage.
On 9th March 2022, at around 1440 hrs, a civil crew involved in soil removal around the exposed LV and HV cables to install form work protection outside of KGP station (100 Meters to the main gate) hit and punctured a HV cable while attempting to loosen the hard strata beneath, using a pickaxe. This resulted in tripping of KGP station. The crew stopped the activity and reported to the Station Operator immediately. At around 1600 hrs, the KGP station resumed operations after rectification by Electrical Team.
Always use non-metallic tools close to live electric cables. Pickaxes shall not be used within 1m distance of any live electric cable. Always be prepared to stop work and ask for advice when faced with challenges. Encourage co-workers to “STOP” any unsafe act. Beware of live electrical cables; follow precautions.
Cable trench designed to be constructed beneath the live LV and HV cables; isolating the cables supplying power to KGP was not feasible . PTW controls, method statement, JHSEP, TRIC are inadequate in terms of specifying the right methodology, tools, safeguard required for this scenario (removing hard strata from beneath the live cables) without isolation. Permit Applicant ignored the risk involved in breaking the hard strata beneath the live cables and assigned the activity to Permit Holder without adequate briefing. Crew tasked with soil removal beside and underneath the exposed cables, encountered hard strata as there was no soft soil spread beneath the cables. Permit Holder did not consider stopping the work and seeking, instead chose to break the hard strata using pickaxe when the soil could not be removed using non-metallic shovel.

Category:Second AlertsDocument Type:Safety
Format:pptx<br/>Viewers:39
Download: